Napa tes DC Hipot dianggep minangka karusakan bisu kanggo kabel XLPE?

 Jun 17, 2026

 Ninggalake pesen

 

P: Kenapa DC Hipot saiki dilarang banget dening standar kaya IEEE 400.1 kanggo kabel XLPE?

 

A: Amarga XLPE minangka polimer padat. Ing lapangan listrik DC sing dhuwur, dheweke ngalami fenomena ngrusak sing diarani Space Charge Accumulation.

 

Mekanisme karusakan:

• Trapping Electron: Tegangan DC drive elektron / ion menyang jampel, njebak ing antarmuka polimer.

• Charge Trapped: Muatan statis tetep kepepet ing insulasi kanggo dina utawa minggu sawise test.

• Power Return AC: Polaritas flipped 50/60 kaping/detik nyebabake kolom AC mundhak kaping pindho - nglawan muatan sing kepepet.

• Asil: Lapangan lokal mundhak (E_total=E_AC + E_space), nyebabake wit cepet lan rusak kanthi cepet.

IEEE Standard View: IEEE 400.1 nyatakake yen tes DC XLPE bisa nyebabake karusakan insulasi permanen. Ora nemokake cacat nyata; iku mung ngrusak bagean sehat.